Model | ZDR-150-12 | ZDR-150-15 | ZDR-150-24 | ZDR-150-36 | ZDR-150-48 | |
Dc output voltage | 12V | 15V | 24V | 36V | 48V | |
Rated current | 115 VAC | 10.2A | 8.5A | 5.3A | 3.6A | 2.7A |
230 VAC | 11.3A | 9.5A | 6.2A | 4.2A | 3.2A | |
Current range | 0-11.3A | 0-9.5A | 0-6.2A | 0-4.2A | 0-3.2A | |
Rated power | 115 VAC | 120W | 125W | 125W | 125W | 130W |
230 VAC | 135W | 142W | 150W | 150W | 150W | |
Ripple & Noise (Max) | 150mVp-p | 150mVp-p | 200mVp-p | 220mVp-p | 240mVp-p | |
Voltage regulation range | 10.9-13.2V | 13.6-16.5V | 21.8-26.4V | 32.7-39.6V | 43.6-52.8V | |
Voltage accuracy | ±1% | ±1% | ±1% | ±1% | ±1% | |
Linear adjustment rate | ±1% | ±1% | ±1% | ±1% | ±1% | |
Load adjustment rate | ±1% | ±1% | ±1% | ±1% | ±1% | |
Start & rise time | 2000mS, 30mS/115VAC(Full load), 1000mS, 30mS/230VAC | |||||
Holding time | 30mS/230VAC(Full load), 10mS/115VAC(Full load) | |||||
Input voltage | 85-264VAC120-370VDC | |||||
Input frequency | 47-63Hz | |||||
efficiency | 87% | 87% | 88% | 88% | 88% | |
Input current | 3A/115VAC1.6A/230VAC | |||||
Power factor | 0.65/230VAC(Full load) | |||||
Inrush current | 70A/230VAC (|Cold start) | |||||
Leakage current | ||||||
Overload protection | 110%-150% of rated power | |||||
Protection mode: hiccup protection, automatically recovered after abnormal conditions are removed | ||||||
Over-current protection | 110%-150% of the rated current | |||||
Protection mode: hiccup protection, automatically recovered after abnormal conditions are removed | ||||||
Short circuit protection | Output positive negative short circuit | |||||
Protection mode: hiccup protection, automatically recovered after abnormal conditions are removed | ||||||
Operating temperature | -30℃~70℃(refer to derating curve) | |||||
Working humidity | 20~90%RH no condensation | |||||
Store temperature/humidity | -40℃to 85℃10~95%RH, no condensation | |||||
Vibration resistance | 10~500HZ, 5G10 minutes/cycle,X, Y, Z 60 minutes each | |||||
Withstand voltage | Input to output :800VAC | |||||
Insulation impedance | Input to output :100MOhms/500VDC/25℃/70%RH | |||||
Safety specification | ||||||
Product size | 150*90*54.5mm(W*H*D) | |||||
package | 0.327kg/pcs | |||||
Note | 1. All parameters are measured at 230VAC voltage input, rated load and 25℃when not specified. 2. Ripple and noise voltage is measured at 20MHz bandwidth oscilloscope with 12-inch twisted pair end with 0.1μ and 47μ capacitance, and measured at 20MHZ bandwidth. 3. Accuracy: including setting error, linear adjustment rate and load adjustment rate. 4. If the input voltage is low, the output needs to be derated. For details, see the static characteristic diagram. | |||||