30W transformer 220v 24v ac industrial din rail 30w power supply
Features:
1.Universal AC input/Full range
2.Installed on DIN rail TS35/7.5 or 15
3.Protections:Short sircut/Overload/Over voltage
4.No load power consumption<0.75w
5.LED indicator for powe on
6.NEC class 2/LPS compliant(slected model)
7.DC OK signal output;DC OK relay contact.
8.Cooling by free air convection
9.100% full load burn-in test.
10. 2 years warranty.
Product Parameters
SPECIFICATIONS |
Model |
DR-30-5 |
DR-30-12 |
DR-30-15 |
DR-30-24 |
OUTPUT |
DC Voltage |
5V |
12V |
15V |
24V |
Rated Current |
3A |
2A |
2A |
1.5A |
Current Range |
0-3A |
0-2A |
0-2A |
0-1.5A |
Rated Power |
15W |
24W |
30W |
36W |
Ripple&Noise |
80mVp-p |
120mVp-p |
120mVp-p |
150mVp-p |
Voltage Adj.Range |
-5%,+10% |
±10% |
±10% |
±10% |
Voltage Tolerance |
±2% |
±1% |
±1% |
±1% |
Setup,Rise,Hold Up Time |
100ms,30ms/230VAC 100ms,30ms/115VAC at full load |
INPUT |
Voltage Range |
85~264VAC 47~63Hz; 120~370VDC |
AC Current |
0.88A/115V 0.48A/230V |
Efficiency |
74% |
81% |
82% |
83% |
Inrush Current |
Cold start 15A 30A/230V |
PROTECTION |
Over Load |
105%~160% |
Protection type:Constant current limiting,recovers automatically after fault condition is removed |
Over Voltage |
115%~135% |
Protection type:Shut down o/p voltage,re-power on to recover |
ENVIRONMENT |
Working Temp.,Humidity |
-10ºC~+60ºC;20%~90%RH |
Storage Temp.,Humidity |
-20ºC~+85ºC;10%~95%RH |
Temp.Coefficient |
±0.03%/ºC(0~50ºC) |
Vibration |
10~500Hz,2G 10min./1cycle,period for 60min,each along X,Y,Z axes |
SAFETY |
Withstand Voltage |
I/P-O/P:100M Ohms / 500VDC |
STANDARD |
Safety Standard |
Design refer to UL60950-1,TUV EN60950-1,EN50178 |
EMC Standard |
Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3 |
OTHERS |
Dimension |
78*93*56mm(L*W*H) |
Weight |
0.27Kg |
Packing |
48pcs/14Kg/1.02CUFT |
Want to learn more, feel free to contact Rina at: