Slim size LRS-150-12 LED power supply 150W 12V single output switching power supply
150W Single Output Switching Power Supply LRS-150 series
Features:
AC input range selectabl by switch
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage/ Over temperature
Cooling by free air convection
LED indicator for power on
100% full load burn-in test
High operating temperature up to 70ºC
High efficiency, long life and high reliability
2 years warranty
more efficient, more thinner, less no-load consumption than old series
Product Description
SPECIFICATION |
|
OUTPUT |
|
Model |
LRS-150-12 |
LRS-150-15 |
LRS-150-24 |
LRS-150-36 |
LRS-150-48 |
DC Voltage |
12V |
15V |
24V |
36V |
48V |
Rated Current |
12.5A |
10A |
6.5A |
4.3A |
3.3A |
Current Range |
0~12.5A |
0~10A |
0~6.5A |
0~4.3A |
0~3.3A |
Rated Power |
150W |
150W |
156W |
154.8W |
158.4W |
Ripple & Noise |
150mVp-p |
150mVp-p |
200mVp-p |
200mVp-p |
200mVp-p |
Voltage Adj. Range |
10.2~ 13.8V |
13.5~18V |
21.6~28.8V |
32.4~39.6V |
43.2~52.8V |
Voltage Tolerance |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
Line Regulation |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
Load Regulation |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
Setup, Rise Time |
500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load |
Hold Up Time |
40ms/230VAC 35ms/115VAC at full load |
|
|
INPUT |
|
Voltage Range |
85 ~ 132VAC / 170 ~264VAC 240 ~ 370VDC(switch on 230VAC) |
Frequency Range |
47 ~ 63Hz |
Efficiency |
87.50% |
88.50% |
89% |
89% |
90% |
AC Current |
2.8A/115VAC 1.6A/230VAC |
Inrush Current |
Cold start 60A/230VAC |
Leakage Current |
<0.75mA / 240VAC |
|
|
PROTECTION |
|
Over Load |
110 ~ 140% rated output power |
Protection type: Hiccup mode, recovers automatically after fault condition is removed |
Over Voltage |
13.8 ~ 16.2V |
18.75~21.75V |
28.8 ~ 33.6V |
41.4~48.6V |
55.2~ 64.8V |
Protection type: shut down o/p voltage, re-power on to recover |
|
|
ENVIRONMENT |
|
Working Temp. |
-30 ~ +70ºC (Refer to "derating curve") |
Working Humidity |
20 ~ 90% RH non-condensing |
Storage Temp., Humidity |
-40 ~ +85ºC, 10 ~ 95% RH |
Temp. Coefficient |
±0.03%/ºC (0 ~ 50ºC) |
Vibration |
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes |
|
|
SAFETY & EMC |
|
Safety Standards |
UL60950-1, TUV EN60950-1, EN60335-1/-2-16, CCC GB4943 approved |
Withstand Voltage |
I/P-O/P:3.75KVAC I/P-FG:2KVAC O/P-FG:1.25KVAC |
Isolation Resistance |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25ºC / 70% RH |
EMC Emission |
Compliance to EN55022(CISPR22), GB9254 CLASS B, EN55014 EN61000-3-2,-3 class A, EN61000-3-3 |
EMC Immunity |
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2(EN50082-2), heavy industry level, criteria A |
|
|
OTHERS |
|
Dimension |
159*97*30mm (L*W*H) |
Weight |
0.48Kg |
Packing |
30pcs/carton/15.4kg/0.75CUFT |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
7. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.