Model |
HDR-60-5 |
HDR-60-12 |
HDR-60-15 |
HDR-60-24 |
HDR-60-48 |
DC Voltage |
5V |
12V |
15V |
24V |
48V |
Rated Current |
6.5A |
4.5A |
4A |
2.5A |
1.25A |
Current Range |
0 ~ 6.5A |
0 ~ 4.5A |
0 ~ 4A |
0 ~ 2.5A |
0 ~ 1.25A |
Rated Power |
32.5W |
54W |
60W |
60W |
60W |
Ripple & Noise (max.) |
80mVp-p |
120mVp-p |
120mVp-p |
150mVp-p |
240mVp-p |
Voltage Adj. Range |
5.0 ~ 5.5V |
10.8 ~ 13.8V |
13.5 ~ 18V |
21.6 ~ 29V |
43.2 ~ 55.2V |
Voltage Tolerance |
±2.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
Line Regulation |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
Load Regulation |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
Setup, Rise Time |
500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load |
Hold Up Time (Typ.) |
30ms/230VAC 12ms/115VAC at full load |
Voltage Range |
85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational ) |
Frequency Range |
47 ~ 63Hz |
Efficiency (Typ.) |
85% |
88% |
89% |
90% |
91% |
AC Current (Typ.) |
1.2A/115VAC 0.8A/230VAC |
Inrush Ccurrent (Typ.) |
COLD START 30A/115VAC 60A/230VAC |
Over Load |
105 ~ 160% rated output power |
Hiccup mode when output voltage <50%, recovers automatically after fault condition is removed |
Constant current limiting within 50% ~100% rated output voltage, recovers automatically after fault condition is removed |
Over Voltage |
5.75 ~ 6.75V |
14.2 ~ 16.2V |
18.8 ~ 22.5V |
30 ~ 36V |
56.5 ~ 64.8V |
Protection type : Shut down o/p voltage, re-power on to recover |
Working Temp. |
-30 ~ +70ºC (Refer to "Derating Curve") |
Working Humidity |
20 ~ 90% RH non-condensing |
Storage Temp., Humidity |
-40 ~ +85ºC, 10 ~ 95% RH non-condensing |
Temp. Coefficient |
±0.03%/ºC (0 ~ 50ºC) RH non-condensing |
Vibration |
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
Operating Altitude |
2000 meters |
Withstand Voltage |
I/P-O/P:4KVAC |
Isolation Resistance |
I/P-O/P:100M Ohms / 500VDC / 25ºC/ 70% RH |
MTBF |
927.6K hrs min. MIL-HDBK-217F (25ºC) |
Dimension |
52.5*90*54.5mm (W*H*D) |
Packing |
190g;60pcs/12.4Kg/0.97CUFT |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. |
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1μf & 47μf parallel capacitor. |
3. Tolerance : includes set up tolerance, line regulation and load regulation. |
4. The power supply is considered as an independent unit, but the final equipment still need to re-confirm that the whole system complies with the EMC directives. For guidance on how to perform these EMC tests, please refer to "EMI testing of component power supplies." |
5. The ambient temperature derating of 3.5ºC/1000m with fanless models and of 5ºC/1000m with fan models for operating altitude higher than 2000m(6500ft). |